CIB – power meter, converter of electrical quantities C-EM-0401M
Основные свойства:
· Module includes inbuilt three-phase four-quadrant electricity meter for indirect measuring using current transformer, with option of automatic deduction and registration in various tariffs.
· Separately registers active energy delivered and consumed. As for idle energy module registers the types of load, capacitive and inductive thus as so-called four-quadrant electricity meter or capacitive and inductive separately in case of separated consumption or supply of active energy as so-called six-quadrant electricity meter.
· Contains 4 independent voltage inputs measured towards neutral wire, 4 inputs to connect external split core (x=‘S‘) or solid core (x=‘P‘) current transformers with nominal current selectable in range from 5 up to 600A.
· Contains 1 relay output controled by protective function implemented in module, which realizes function of voltage and frequency protection. Range of monitored voltage and frequency including reaction times and time of repeated restoration after subsiding, the cause of protection activation can be set trough parameters in SW Mosaic.
· Module is made in 3 basic series (z=‘‘, ‚L‘ and ‚S‘) according to level of auxiliary supply voltage.
Connection:
· Module needs to be connected with 2 wire CIB bus, which ensures communication of module with basic module.
· Electricity meter module is powered by ancillary voltage supply in 3 altering respectively direct optional variants.
· Module needs to be connected with 2 wire CIB bus, which ensures communication of module with basic module.
· Measuring inputs, power supply, relay output and CIB bus are led out on non-removable screw-type terminals.